三菱电机家庭中央空调安装标准
一、现场施工要求······································2今天是愚人节吗
二、设备的摆放·······································2
三、材料的摆放·······································3
四、设备的安装·······································3-4
五、套管的安装·······································5
六、固定码的安装··································5~6
七、冷媒管的安装··································6~7
八、排水管的安装··································8~9
九、保温作业·····································9~10
十、试压作业········································10
十一、配线作业·······································11
一、现场施工要求
1 公司统一的服装;
2 佩戴施工牌;
3 配戴安全帽;
4 张贴现场提示牌;
5 文明施工、安全施工;
二、设备的摆放
1 堆放场所应具备防水、防尘、防晒条件;
2 设备应按外包装标示堆放;
3 室内机堆放的层数,不可超过设备外包装上的标示要求,面板不可超过24层;
4 设备包装完好;
5 禁止踩踏;
6 设备按外包装标示堆放;
7 室外机堆放的层数不可超过外包装上的标示要求;
8 设备包装完好;
三、材料的摆放
1 堆放场所应具备防水、防尘、防晒条件;
2 冷媒管清洁后应做好封口处理;
联字组词
3 冷媒管离地300mm以上搁置堆放,并防止碰撞受损;
4 保温材料按型号包装好;
5 保持保温材料内外表面干净清洁;
6 排水管按型号进行堆放;
7 按不同的材料类型、规格分类摆放,标识清楚;
四、设备的安装
室内机安装
1 室内机吊装下方双螺母固定;
2 丝杆不小于Φ10mm(内机用吊耳吊装,不能用拉爆);
3 丝杆要保持垂直;
4 丝杆的长度统一在机器的中间位置;
5 室内机水平安装±1°以内 ;
6 室内机有足够的送回风空间;
7 室内机有足够的维修、保养空间(建议做独立的检修口);
8 吊装室内机后应及时全方位防尘保护;
9 维修口尺寸应350×350mm以上;
室外机安装
1 室外机水平安装±1°以内;
2 室外机应保证足够的散热空间;
3 室外机的噪音应不影响到用户或是他人;
4 室外机排风应不影响到他人;
5 室外机应有足够的维修空间;
6 室外机基础高度200mm以上;
7 室外机基础加防震垫;
移动商城积分
8 防震垫厚度不小于10mm;
9 室外机安装位置便于排水;
10 当室外机在室内时,分层摆放应安装排风导管;
11  移除室外机风扇出风口处的导风隔栅;
12 风管边缘紧贴百叶根部,确保无缝隙;
13 建筑百叶的导风角度应小于与水平夹角20度,百叶的通风率不小于70%;
14 风管与设备采用柔性连接,帆布高度150~300mm;
15 应保障气流循环的回风空间,以及安装、维护所需空间;
16 室外的送、回风管的间距为风管直径的3倍以上;
五、套管的安装
1 冷媒管穿越楼板,应做好防水的施工工作;
2 冷媒管穿越屋顶防雨屋时应与土建密切配合,作好防水的施工工作;
3 冷媒管贯通后室外侧应有一定向下的坡度,防止水回流;
4 冷媒管或排水管穿墙加套管保护;
5 套管的长度与装修后的墙体厚度相等;
6 套管内的缝隙应用阻燃烧材料填满;
7 建力墙、有防火要求的应按防火要求使用套管材料;
8 冷媒管、排水管穿墙应套管保护;
9 套管内的缝隙应用阻燃烧材料填满;
六、固定码的安装
1 确定冷媒管、排水管的走向和定位;
2 安装冷媒管、排水管前应先安装固定码;
立夏为什么要斗蛋
3 冷媒管、排水管的固定码间隔要统一美观,固定间距应在三菱电机的技术要求内;